Viessmann Vitodens 200 Service Instructions Manual page 37

Type wb2a, 8.8 to 20.0 kw wall mounted gas fired condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Code 1
(cont.)
Coding in the delivered condition
User no.
77:1
LON user number
Summer econ. A1/M2
A5:5
With heating circuit
pump logic function
(only for weather-com-
pensated control units)
Min. flow temp. A1/M2
C5:20
Electronic minimum
flow temperature limit
20 °C (only for weather-
compensated control
units)
Max. flow temp. A1/M2
C6:75
Electronic maximum
flow temperature limit
75 °C (only for weather-
compensated control
units)
Slope A1/M2
d3:14
Heating curve slope =
1.4 (only for weather-
compensated control
units)
Level A1/M2
d4:0
Heating curve level = 0
(only for weather-com-
pensated control units)
Possible change
77:2
LON user number, adjus-
to
table from 1 to 99:
77:99
1 - 4 = Boiler
5 = Cascade
10 - ... = Vitotronic 050
99 = Vitocom
Note
Allocate each number
only once.
A5:0
Without heating circuit
pump logic function
C5:1
Minimum limit adjustable
to
from 1 to 127 °C (limited
C5:127
by the boiler coding card)
C6:10
Maximum limit adjustable
to
from 10 to 127 °C
C6:127
d3:2
Heating curve slope ad-
to
justable from 0.2 to 3.5
d3:35
(see page 28)
d4: 13
Heating curve level ad-
to
justable from 13 to 40
d4:40
(see page 28)
Coding
37