Code 2
(cont.)
Coding in the delivered condition
E9:45
Speed of the external
variable speed heating
circuit pump 45 % of the
max. speed during op-
eration with reduced
room temperature (only
for weather-compen-
sated control units)
F1:0
Screed drying function
disabled (only for
weather-compensated
control units).
F2:8
Time limit for party
mode or external oper-
ating mode changeover
via key: 8 hours (only
for weather-compen-
sated control units)
F5:12
Run-on time of the inter-
nal circulation pump in
heating mode 12 min
(only for constant tem-
perature control units)
F6:25
In the "DHW only" oper-
ating mode, the internal
circulation pump is per-
manently ON (only for
constant temperature
control units)
*1
Party mode ends automatically in the "Heating and DHW" program, when the system
changes over to operation with standard room temperature.
Possible change
E9:0
Speed adjustable from 0
to
to 100 % of the maximum
E9:100
speed during operation
with reduced room tem-
perature
F1:1
Screed drying function
to
adjustable in accordance
F1:5
with five optional tem-
perature/time profiles
(see page 95)
F1:6
Constant flow tempera-
to
ture 20 °C
F1:15
F2:0
No time limit for party
mode
F2:1
Time limit adjustable from
to
1 to 12 hours
F2:12
*
1
F5:0
No run-on time of the in-
ternal circulation pump
F5:1
Run-on time of the inter-
to
nal circulation pump ad-
F5:20
justable from 1 to 20 min
F6:0
In the "DHW only" operat-
ing mode, the internal cir-
culation pump is
permanently OFF
F6:1
In the "DHW only" operat-
to
ing mode, the internal cir-
F6:24
culation pump will be
started 1 to 24 times per
day for 10 min respec-
tively.
Coding
*
1
55