Commissioning, inspection, maintenance
Further details regarding the individual steps
Yes
Ignition
Yes
Gas combination
valve opens
Yes
Ionisation cur-
rent builds
(higher than
5 µA)
Symbol A
Yes
Burner in opera-
No
tion
For further details regarding faults, see page 68.
12
Fault F4
No
Fault F4
No
Fault F4
No
Stops below the
set boiler water
temperature and
restarts immedi-
ately
(cont.)
Check ignition
module (control
voltage 230 V
across plugs
"X2.1" and
"X2.2")
Check the gas
combination valve
(control voltage
230 V); check the
gas supply pres-
sure
Check the ionisa-
tion current,
check the elec-
trode adjustment
and the gas pipe
for airlocks
Check flue gas
system for sound-
ness (flue gas re-
circulation),
check gas flow
pressure