Step 6: Connect Power Cables

IN THIS SECTION

Connect Power to an AC-Powered Services Gateway | 17

Connect Power to a DC-Powered Services Gateway | 21
Depending on its configuration, the services gateway uses either AC or DC power supplies. Perform the
appropriate procedures for each power supply in the services gateway.
Connect Power to an AC-Powered Services Gateway
This procedure addresses connecting power to services gateways equipped with either standard-capacity
or high-capacity AC power supplies.
WARNING:
to ensure proper operation, you must properly ground the services gateway chassis
before connecting power. See
instructions.
NOTE:
The services gateway must be running Junos OS Release 10.4 or later in order to use
high-capacity AC power supplies.
NOTE:
The device is not shipped with AC power cords. Make sure to order or obtain AC power
cords with a plug appropriate for your geographical location.
To meet safety and electromagnetic interference (EMI) requirements and
"Step 4: Connect the Grounding Cable" on page 13