Siemens SIMOTION Function Manual page 27

Motion control, output cams and measuring inputs
Hide thumbs Also See for SIMOTION:

Advertisement

Note
Further information and the output accuracy for high-speed output cams is described in the
PM21 Catalog and in the respective product brief or commissioning/equipment manuals.
Commissioning Manual
Operating Instructions
Commissioning Manual
Commissioning Manual
Commissioning and Hardware Installation Manual
Commissioning and Hardware Installation Manual
See also
Configuring cams on SIMOTION D4xx onboard (Page 47)
3.2.1.8
Exact time setting of an output, exact time output cams (as of V4.1)
You can switch a high-speed output cam On/Off at an exact time within an execution cycle
(position control, IPO cycle) via the timeOffset parameter of the _setOutputCamState system
function.
Enter an offset of the switching edge in the configured unit (e.g. s) of the Output Cam TO in
the timeOffset parameter. The reference point of the offset is the start of the next execution
cycle of the Output Cam TO. You can read out the value of the time offset (system-dependent
execution time between the execution cycle and the output cycle) in the tOutput system
variable. The time in tOutput is the earliest possible time to switch the output cam. The
timeOffset is added to this time.
Features
● The offset must be less than the cycle time of the processing cycle clock. The offset is
● It is possible to switch on or off within one cycle.
● When this function is used, there is a dependency on the processing cycle clock and the
● The offset is valid for every output cam type. If only switched once, the unidirectional output
● The offset can only be stated if the output cam TO on the outputs is configured with a time
● For output cams without time stamp (e.g. C240-2 onboard output cams), tOutput (time
Output Cams and Measuring Inputs
Function Manual, 04/2014
Terminal Modules TM15/TM17 High Feature
SIMOTION C2xx
SIMOTION D410
SIMOTION D410-2
limited automatically and a technological alarm is output when the cycle time is exceeded.
set cycle clock times.
cam type is recommended.
stamp (cam output (CAM)).
stamp) is set to 0.0.
Output Cam TO - Part I
3.2 Output cam TO basics
SIMOTION D4x5
SIMOTION D4x5-2
27