Measuring Input TO - Part III
5.3 Configuring the Measuring Input technology object
5. Double-click Telegram configuration and, in the window that opens, select the tab
Figure 5-17
Determining the hardware address of the components
6. Before you determine the hardware address, an alignment between HW Config and
7. Now calculate the HW address by adding the base input address (first value of the address
8. The bit number is defined by means of the offset. For example, an offset of 3.0 results in a
See also
Inserting Measuring Inputs (Page 153)
Parameterization of the Measuring Input technology object (Page 153)
166
PROFIdrive PZD telegrams. The components are displayed there with the address ranges
(e.g. TM17 input data 288...299).
SIMOTION SCOUT, with respect to the address, must be performed. If this has not been
performed or you have changed the addresses, click on Set up addresses. If there are
question marks in the fields instead of I/O addresses, you must also perform an alignment.
range) of the TM to the offset (for example 288 + 3 = 291).
bit number of 0.
Output Cams and Measuring Inputs
Function Manual, 04/2014