Siemens SINAMICS G130 Engineering Manual page 250

Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

SINAMICS S120 Cabinet Modules
Engineering Information
Active Line Modules + Active Interface Modules
Active Infeeds must be regarded as requiring two separate auxiliary voltage supplies, i.e. one for the Active Interface
Module (AIM) and one for the Active Line Module (ALM).
The AIM requires the following voltages:
24 V DC:
Control electronics
230 V AC:
Cabinet ventilation, control voltage of precharging contactors depending on type
The ALM requires the following voltages:
24 V DC:
Control electronics
400 V resp. 690 V AC: Power unit fans
Active Interface Modules and Active Line Modules together are delivered due to the required performance
connections as one unit. For this reason, the AIM's auxiliary voltage connections are already made to the ALM's
auxiliary voltage busbar when the unit is delivered. Fuse protection down-circuit of the auxiliary voltage busbar is
provided in the Cabinet Modules.
The power requirement in the table below is based on a combination of Active Interface Module and Active Line
Module.
Order No.
Frame
size
Supply voltage 380 V – 480 V 3AC (DC link voltage 570 V – 720 V)
6SL3730-7TE32-1BA0
FX+FI
6SL3730-7TE32-6BA0
FX+FI
6SL3730-7TE33-8BA0
GX+GI
6SL3730-7TE35-0BA0
GX+GI
6SL3730-7TE36-1BA0
HX+HI
6SL3730-7TE38-4BA0
HX+HI
6SL3730-7TE41-0BA0
JX+JI
6SL3730-7TE41-0BC0
JX+JI
6SL3730-7TE41-4BA0
JX+JI
6SL3730-7TE41-4BC0
JX+JI
Supply voltage 500 V – 690 V 3AC (DC link voltage 750 V – 1035 V)
6SL3730-7TG35-8BA0
HX+HI
6SL3730-7TG37-4BA0
JX+JI
6SL3730-7TG37-4BC0
JX+JI
6SL3730-7TG41-0BA0
JX+JI
6SL3730-7TG41-0BC0
JX+JI
6SL3730-7TG41-3BA0
JX+JI
6SL3730-7TG41-3BC0
JX+JI
1)
Power requirement of Control electronics, auxiliary power supply for fans.
SINAMICS Engineering Manual – May 2008
250/396
© Siemens AG
Rated rectifier/
Rated rectifier/
Current requirement
regenerative
regenerative
power at 400 V
current
resp 690 V
I
rated
[kW]
[A]
132
210
160
260
235
380
300
490
380
605
500
840
630
985
630
985
900
1405
900
1405
560
575
800
735
800
735
1100
1025
1100
1025
1400
1270
1400
1270
1)
24 V
230 V AC
DC
50 Hz
60 Hz
[A]
[A]
1.27
0.3
1.27
0.3
1.52
0.65
1.52
0.65
1.57
3.4
1.57
3.4
1.67
3.5
1.67
3.5
1.87
3.5
1.87
3.5
1.57
3.4
1.67
3.5
1.67
3.5
1.87
3.5
1.87
3.5
1.87
3.5
1.87
3.5
400 V resp. 690V AC
50 Hz
[A]
[A]
0.4
0.5
0.4
1.4
0.93
1.8
0.93
1.8
4.8
3.6
4.8
3.6
4.9
5.4
4.9
5.4
4.9
5.4
4.9
5.4
4.8
2.1
4.9
3.2
4.9
3.2
4.9
3.2
4.9
3.2
4.9
3.2
4.9
3.2
60 Hz
[A]
0.6
2.0
2.6
2.6
5.3
5.3
7.9
7.9
7.9
7.9
3.1
4.7
4.7
4.7
4.7
4.7
4.7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s120 chassisSinamics s150

Table of Contents