SINAMICS G150
Engineering Information
Due to the design principle of using two separate, low-output converter cabinet units, the configuration includes two
each of the following components:
Mains supply connections
Main switch and main contactors
All power unit components
Motor connections
A parallel connection features only one of each of the following:
CU320 Control Unit, which controls and synchronizes both individual power units
AOP30 operator panel
TM31 customer interface (analog and digital inputs and outputs)
Note:
In contrast to the S120 Infeed Modules and the S120 Motor Modules of the SINAMICS S120 modular system
(Chassis and Cabinet Modules) in which up to four individual modules can be combined to a parallel connection, the
G150 parallel converter / G150 power extension is a ready-to-connect converter cabinet unit comprising two
converter cabinet units with lower outputs. It is ordered and supplied as a single unit with one order number. The
technical data provided in the catalogs and in the tables of this engineering manual always refer to the complete
G150 parallel converter and include already the current and power derating factors required for parallel connections.
The table below shows the power spectrum of the SINAMICS G150 parallel converters. For information purposes
only, the last column contains the rated output current of the relevant individual cabinet units on which the parallel
converter is based.
Rated output
Low overload
current
P
L
[A]
[kW]
Line supply voltage 380 V - 480 V 3AC
1120
630
1380
710
1560
900
Line supply voltage 500 V - 600 V 3AC
860
630
1070
710
1360
1000
Line supply voltage 660 V - 690 V 3AC
1070
1000
1360
1350
1500
1500
Power range of SINAMICS G150 parallel-connected converters
Since SINAMICS G150 parallel converters consist of two identical rectifiers on the line side, the rectifiers can operate
either in 6-pulse or in 12-pulse configuration. The harmonic effects on the supply system are significantly lower in the
12-pulse operation than in the 6-pulse operation (see section "Harmonic effects on supply system" of the chapter
"Fundamental Principles and System Description").
On the line side, certain conditions must be taken in account depending on whether the configuration is a 6-pulse or a
12-pulse configuration.
On the motor side, limitations exist related to the necessary minimum cable lengths for the motor and also to the
permissible pulse modulation systems of the inverter, depending on the winding system in the motor (electrically
isolated winding systems or one common winding system).
The following information describes the possible line-side and motor-side configurations of SINAMICS G150 parallel
converters and the associated supplementary conditions that have to be taken in account.
SINAMICS Engineering Manual – May 2008
204/396
© Siemens AG
High overload
Base load
Base load
P
H
current I
current I
L
[A]
[kW]
[A]
1092
500
850
1340
560
1054
1516
710
1294
836
560
770
1036
630
950
1314
800
1216
1036
900
950
1314
1200
1216
1462
1350
1340
Order number
H
6SL3710-2GE41-1AA0
6SL3710-2GE41-4AA0
6SL3710-2GE41-6AA0
6SL3710-2GF38-6AA0
6SL3710-2GF41-1AA0
6SL3710-2GF41-4AA0
6SL3710-2GH41-1AA0
6SL3710-2GH41-4AA0
6SL3710-2GH41-5AA0
The parallel device is constructed
of two individual units with a
rated output current of
[A]
605
745
840
465
575
735
575
735
810