Cooling air requirements

A specific quantity of cooling air must be supplied to S120 Cabinet Modules. This cooling air requirement is always
important, even under challenging boundary conditions. The cooling air is drawn in from the front through the
ventilation grilles in the lower part of the cabinet doors. The warmed air is expelled through the perforated top cover
or the ventilation grilles in the top cover (with option M23/ M43/ M54). The minimum ceiling height (for unhindered air
outlet) specified in the dimension drawings must be observed. Cooling air can also be supplied from below through
raised floors or air ducts, for example. Openings in the 3-section baseplate must be made for this purpose. Please
also refer to the supplementary information for option M59 (cabinet door closed).
The cooling air requirement of individual Cabinet Modules is specified in the tables below:
Line Connection Modules
Frame size
I
[A]
rated
Supply voltage 380 V to 480 V 3AC
FL
250
FL
400
GL
630
HL
800
JL
1000
JL
1250
JL
1600
KL
2000
KL
2500
LL
3200
Basic Line Modules
P
at 400 V
rated
Frame size
[kW]
Supply voltage 380 V to 480 V 3AC
FB
200
FB
250
FB
400
GB
560
GB
710
GD
900
Smart Line Modules
P
at 400 V
rated
Frame size
[kW]
Supply voltage 380 V to 480 V 3AC
GX
250
GX
355
HX
500
JX
630
JX
800
1
Components use natural convection
2
Fan for degree of protection IP23, IP43, IP54 (in combination with Basic Line Modules)
Cooling air requirement
[m³/s]
1
-
1
-
1
-
1
-
1,2
0.36
1,2
0.36
1,2
0.36
1,2
0.72
1,2
0.72
1,2
0.72
Cooling air requirement
[m³/s]
0.17
0.17
0.17
0.36
0.36
0.36
Cooling air requirement
[m³/s]
0.36
0.36
0.78
1.08
1.08
SINAMICS S120 Cabinet Modules
Line Connection Modules
Frame size
I
[A]
rated
Supply voltage 500 V to 690 V 3AC
FL
280
FL
400
GL
630
HL
800
JL
1000
JL
1250
JL
1600
KL
2000
KL
2500
LL
3200
Basic Line Modules
P
at 690 V
rated
Frame size
[kW]
Supply voltage 500 V to 690 V 3AC
FB
250
FB
355
FB
500
GB
900
GB
1100
GD
1500
Smart Line Modules
P
at 690 V
rated
Frame size
[kW]
Supply voltage 500 V to 690 V 3AC
GX
450
HX
710
JX
1000
JX
1400
SINAMICS Engineering Manual - May 2008
Engineering Information
Cooling air requirement
[m³/s]
1
-
1
-
1
-
1
-
1,2
0.36
1,2
0.36
1,2
0.36
1,2
0.72
1,2
0.72
1,2
0.72
Cooling air requirement
[m³/s]
0.17
0.17
0.17
0.36
0.36
0.36
Cooling air requirement
[m³/s]
0.36
0.78
1.08
1.08
245/396
© Siemens AG

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s120 chassisSinamics s150

Table of Contents