Supply systems and supply system types

General

The low-voltage products in the SINAMICS series with line supply voltages of ≤ 690 V are normally connected to
industrial supply systems that are supplied from the medium-voltage distribution system via transformers. In rare
cases, however, these devices may be directly connected to the public low-voltage supply systems or to separate
supply systems, such as those supplied by diesel-electric generators.
According to IEC 60364-3 supply systems are classified as either TN, TT or IT systems depending on the type of
arrangement of the live parts, the exposed-conductive parts and the grounding method. The classifications and
letters are explained in brief below.
First letter: Relationship of the supply system to ground:
T =
Direct connection of one point to ground.
I =
All live parts isolated from ground, or one point connected to ground through an impedance.
Second letter: Relationship of the exposed-conductive parts (enclosures) of the installation to ground:
T =
Direct electrical connection of the exposed-conductive parts (enclosures) to ground, independent of
whether one point of the supply system is already grounded.
N =
Direct electrical connection of the exposed-conductive parts (enclosures) to the grounded point of the
supply system (the grounded point of the supply system is generally the star point in three-phase
systems, or one of the three phases if the system has no star point).
In TN systems, one point is directly grounded and the exposed-conductive parts (enclosures) of the electrical
installation are connected to the same point via a protective conductor (protective earth PE).
Example of a TN supply system
In TT systems, one point is directly grounded and the exposed-conductive parts (enclosures) of the installation are
connected to ground electrodes which are electrically independent of the ground electrodes of the supply system.
Example of a TT supply system
Fundamental Principles and System Description
Engineering Information
SINAMICS Engineering Manual - May 2008
© Siemens AG
21/396