SINAMICS G130
Engineering Information
3.
The converter is controlled via the PROFIBUS interface which is integrated as standard. The digital inputs and
outputs on the Control Unit as well as the optional customer interface TM31 are used to incorporate external
alarm and/or error messages and control signals.
Terminal block on CU320
-X122
Factory setting
DI0
Not assigned
DI1
Not assigned
DI2
Not assigned
DI3
Not assigned
M1
M1
DI/DO8
Not assigned
DI/DO9
Not assigned
M (GND)
DI/DO10
Not assigned
DI/DO11
Not assigned
M (GND)
-X132
DI4
Not assigned
DI5
Not assigned
DI6
Not assigned
DI7
Not assigned
M (GND)
DI/DO12
Error message acknowledgement, Braking
Module
DI/DO13
Not assigned
M (GND)
DI/DO14
Not assigned
DI/DO15
Not assigned
M (GND)
The factory settings of the bidirectional inputs/outputs are underscored.
Terminal block on TM31
Factory setting
-X520
Optocoupler inputs connected to common
potential
DI0
Not assigned
DI1
Not assigned
DI2
Not assigned
DI3
Acknowledge fault
-X530
Optocoupler inputs connected to common
potential
DI4
OFF 2
DI5
OFF 3
DI6
External fault
DI7
Not assigned
1)
A jumper must be inserted here if these inputs are not used
SINAMICS Engineering Manual – May 2008
176/396
© Siemens AG
1)
1)
1)
Comment
Factory-set as output
Factory-set as output
Factory-set as output
Factory-set as output
Output is used (reserved) in conjunction with the Braking
Module
Factory-set as output
Factory-set as output
Factory-set as output
Comment
Immediate pulse disable, motor coasts to standstill
Ramp-down along quick-stop ramp, only of relevance in
conjunction with the Braking Module