Electropneumatic positioner for linear and part--turn actuators
Table of Contents

Advertisement

.
.
SIPART PS2 PA Manual
A5E00127926--05
4.
Switch on to the following display with the operation mode key
5.
Start initialization by pressing the key
Display:
During the initialization phase "RUN1" to "RUN5" appear one after
another in the bottom display (see also structograms figures 49,
page 85 to figure 52, page 88).
NOTE
The initialization process may last up to 15 minutes depending on the
actuator.
The initialization is complete when the following display appears:
The following display appears after pressing the operation mode key
briefly:
To exit the Configuration mode, press the operation mode key
longer than 5 s. The software version is displayed after about 5 s. The
instrument is in manual operation after releasing the operation mode
key.
NOTE
You can abort an ongoing initialization at any time by pressing the
operation mode key. Your previous settings are retained. All the
parameters are reset to the factory setting only after performing a
"Preset".
Preparing for operation
for longer than 5 s.