Siemens 6DR55 Series Manual page 157

Electropneumatic positioner for linear and part--turn actuators
Table of Contents

Advertisement

Event
Run--time error of the
drive
Device not in 'auto-
matic mode'
Binary input BIN1 is
active (only signal)
Action triggered by
binary input 1
Binary input BIN2 is
active (only signal)
Action triggered by
binary input 2
Limit value for path in-
tegral (100% strokes)
exceeded
Limit value for direction
changes exceeded
Limit value for the bot-
tom hard stop monitor-
ing exceeded
Limit value for the top
hard stop monitoring
exceeded
Limit values for dead
zone monitoring ex-
ceeded
Permissible tempera-
ture inside the device
exceeded
Table 14
Configurable diagnostic events and their default representation in status and DIAGNOSIS
Event
Limit for A1 exceeded
Limit for A2 exceeded
Error in electronic of device
The device is not yet opera-
tional (not initialized)
The device is not yet opera-
tional (initializing error)
Function block out of service
Function block out of service
Device in MAN mode
SIPART PS2 PA Manual
A5E00127926--05
The following two tables show the configurable diagnosis events. The
available option is specified in the "Option" column. An "M", for exam-
ple, means that only the DIAGNOSIS bits and the quality status with
the option "M" are available. The meanings of "M", "F" and "P" have
been defined in the two previous tables.
Default values of DIAG_EVENT_SWITCH
Quality Status Code
Bad, maintenance alarm
Bad, function check
Good, maintenance de-
mand
Good, maintenance de-
mand
Good, maintenance re-
quirement
Good, maintenance de-
mand
Good, maintenance re-
quirement
Good, maintenance re-
quirement
Good, maintenance re-
quirement
Good, maintenance re-
quirement
Good, maintenance re-
quirement
Uncertain, process re-
lated
Quality Status Code
Good, active critical alarm
Good, active critical alarm
Bad, maintenance alarm
Bad, maintenance alarm
Bad, maintenance alarm
Bad, passivated
Bad, passivated
Depends on simulated quality
status
Functions/operation via PROFIBUS PA
DIAGNOSIS bit
DIA_MAINTENANCE_ALARM
DIA_FUNCTION_CHECK
DIA_MAINTENANCE_DE-
MANDED
DIA_MAINTENANCE_ALARM
DIA_MAINTENANCE_DE-
MANDED
DIA_MAINTENANCE_ALARM
DIA_MAINTENANCE_RE-
QUIRED
DIA_MAINTENANCE_RE-
QUIRED
DIA_MAINTENANCE_DE-
MANDED
DIA_MAINTENANCE_RE-
QUIRED
DIA_MAINTENANCE_RE-
QUIRED
DIA_INV_PRO_COND
Fixed settings
DIAGNOSIS bit
DIAG_PROCESS_TOLERANCE
DIAG_PROCESS_TOLERANCE
DIA_MAINTENANCE_ALARM
DIA_MAINTENANCE_ALARM
DIA_MAINTENANCE_ALARM
DIA_FUNCTION_CHECK
Possible selection
(Group)
M
F
M,F,P
M,F,P
M,F,P
M,F,P
M
M
M
M
M
M,P
155