Sia Module - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Technical data
12.8 Option modules
For connecting to circuits with the
following peak values
Effective internal capacitance
Effective internal inductance
Galvanic isolation
Test voltage
12.8.3

SIA module

SIA module
Limit encoder with slotted initiators
and fault message output
2 slotted initiators
Binary output (limit transmitter) A1: Terminals 41 and 42
Binary output (limit transmitter) A2: Terminals 51 and 52
Connection
Signal state High
(not triggered)
Signal state Low (triggered)
2 slotted initiators
Function
Connecting to circuits with the
following peak values
Effective internal capacitance
Effective internal inductance
252
Without explosion protec-
tion or suitable for use in
the SIPART PS2 Ex d
-
-
Safe galvanic isolation from alarm option and basic device
Without Ex protection
6DR4004-8G
2 wire technology in accordance with EN 60947-5-6 (NAMUR), for switching
amplifiers connected on load side
NC contact (NC, normally closed)
Nominal voltage 8 V;
current consumption:
≥ 3 mA (limit not activat-
ed),
≤ 1 mA (limit activated)
-
-
With Ex protection Ex ia
(only in temperature class
T4)
U
= DC 30 V
i
I
= 100 mA
i
P
= 1 W
i
C
= 11 nF
i
L
= negligibly small
i
DC 840 V, 1 s
With Ex protection Ex "ia"
6DR4004-6G
> 2.1 mA
< 1.2 mA
Type SJ2-SN
U
= DC 15 V
i
I
= 25 mA
i
P
= 64 mW
i
C
= 41 nF
i
L
= 100 μH
i
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
With Ex protection
Ex "ic", "nA", "t"
"ic":
U
= DC 30 V
i
I
= 100 mA
i
"nA"/"t":
U
≤ DC 30 V
n
I
≤ 100 mA
n
P
≤ 1 W
n
C
= 11 nF
i
L
= negligibly small
i
With Ex protection Ex "ic",
"nA", "t"
6DR4004-6G
"ic":
U
= DC 15 V
i
I
= 25 mA
i
"nA":
U
≤ DC 15 V
n
P
≤ 64 mW
n
C
= 41 nF
i
L
= 100 μH
i

Advertisement

Table of Contents
loading

This manual is also suitable for:

6dr53 series6dr51 series6dr52 seriesSipart ps2

Table of Contents