Message
Line
Up
Down
NOZZL
X
TESt
X
LEAKG
X
nn.n
X
%/MIN
X
nn.n
X
FINISH
X
See also
System messages before initialization (Page 199)
10.1.3
System messages when exiting the Configuration mode
Remarks about the tables:
nn
/
Messages when exiting the configuration mode:
Message
Goals
Up
Down Automatic
n.nn.nnV
X
ER
X
Er-
X
rorSLnn
X
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
Meaning / cause
Actuator stops (the initialization process was
interrupted using the "-" button when the
actuation speed display was active)
Leakage test active (the "+" button was
pressed when the actuation speed display
was active)
Value and unit of the result after the leakage
test
Initialization completed successfully with the
display of actuator travel or the actuator
angle
stands for variable numeric values
Error symbol
(slash): the text to the left and right of the slash blink interchangeably.
Operating mode
Manual mode
10.1 Output of system messages in the display
Measure
The travel time can be changed by ad-
•
justing the restrictor(s)
Redetermine the speed of shifting using
•
the "-" button
Continue with the "+" button
•
Wait for 1 minute
•
Continue with the "+" button
•
Rectify the leakage if the value is too
•
large
Continue with the "+" button
•
Acknowledge by pressing the operating
•
mode button briefly and exit the configu-
ration level by pressing it longer
Meaning / Cause
P Manual mode
Software version
Monotony interruption
of the free character-
istic on the setpoint
turning point n
Alarm, error, and system messages
Measure
Wait
•
Correct value
•
203