Connection

5.1

Basic safety instructions

Improper power supply
Danger of explosion in hazardous areas as result of incorrect power supply, e.g. using
direct current instead of alternating current.
• Connect the device in accordance with the specified power supply and signal circuits.
Unsafe extra-low voltage
Danger of explosion in hazardous areas due to voltage flashover.
• Connect the device to an extra-low voltage with safe isolation (SELV).
Connecting device in energized state
Danger of explosion in hazardous areas.
• Connect devices in hazardous areas only in a de-energized state.
Exceptions:
• Circuits of limited energy may also be connected in the energized state in hazardous
• Exceptions for type of protection "Non-sparking nA" (Zone 2) are regulated in the
Lack of equipotential bonding
Danger of explosion through compensating currents or ignition currents through lack of
equipotential bonding.
• Ensure that the device is potentially equalized.
Exception: It may be permissible to omit connection of the equipotential bonding for devices
with type of protection "Intrinsic safety Ex i".
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
WARNING
The relevant specifications can be found in the certificates, in Chapter "Technical data
(Page 241)" or on the nameplate.
WARNING
WARNING
areas.
relevant certificate
WARNING
5
69