Diagnostics Parameters '23.Impup' Impulse Length Up / '24.Impdn' Impulse Length; Down; Diagnostics Parameter '25.Pautp' Interpulse Period; Diagnostics Parameters '26.Dbup' Deadband Up / '27.Dbdn' Deadband Down - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Alarm, error, and system messages
10.2 Diagnostics
10.2.3.20

Diagnostics parameters '23.IMPUP' Impulse length UP / '24.IMPDN' Impulse length

DOWN

Display range:
Purpose:
Factory setting:
See also
Control algorithm (Page 27)
Optimization of controller data (Page 111)
10.2.3.21

Diagnostics parameter '25.PAUTP' Interpulse period

Display range:
Purpose:
Factory setting:
See also
Control algorithm (Page 27)
10.2.3.22

Diagnostics parameters '26.DBUP' Deadband UP / '27.DBDN' Deadband DOWN

Display range:
Purpose 1
Factory setting:
218
6 ... 160
The smallest impulse lengths that can be used to move the actua-
tor are determined during the initialization process. They are sepa-
rately determined for the "Up" and "Down" directions and displayed
here. Display in ms.
These two parameters can be set for special applications.
6
2 ... 320
The value for the "25.PAUTP" parameter is factory-set to 28 ms.
This value is not changed during an initialization process. Display
in ms.
For applications with high stiction (slipstick), adjusting this parame-
ter improves the control quality.
This parameter can be set for special applications.
28
26.DBUP: 0.1 ... 10.0
27.DBDN: -01. ... 10.0
In this parameter, you can read the deadbands of the controller in
the "Up" and "Down" directions. Display in percent. The values
correspond either to the manually configured value of the
"'34.DEBA' Deadband of closed-loop controller (Page 163)" param-
eter or to the value automatically adapted by the device if "DEBA"
was set to "Auto".
10.0
SIPART PS2 with and without HART