47._Fct' Function Fault Message Output - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

9.4.2.16

'47._FCT' Function fault message output

Requirement:
Possible settings:
Purpose:
Factory setting:
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
At least one of the following modules is fitted
• Alarm module
• Slot initiator alarm module (SIA module)
• Mechanical limit switch module
Normal direction of action
nA
nAb
The fault message in the form of monitoring of control deviation
over time can also be triggered due to the following events:
• Power failure
• Processor fault
• Actuator fault
• Valve fault
• Compressed air failure
• Threshold-3 error message of extended diagnostics.
See "'52.XDIAG' Activating for extended diagnostics
(Page 174) parameter - Activating for extended diagnostics".
Note that the fault message cannot be switched off. It can however
be suppressed (factory setting) when you switch over to "No au-
tomatic mode". If you also want to generate a fault message here,
you will need to set the "47. FCT" parameter to " nA".
You also have an option to "or" the fault message with the status
of the binary inputs. For this purpose, set the "47. FCT" parame-
ter to " nAb".
Select the "- " setting if you want the fault message to be output
with inverted direction of action.
Parameterizing/addressing
9.4 Description of parameters
Inverted direction of action
• -
• - nA
• - nAb
171