System Messages During Operation - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Alarm, error, and system messages
10.1 Output of system messages in the display
10.1.4

System messages during operation

Remarks about the tables:
nn
/
Messages during operation
Message
Line
Abov
Below Automatic
e
CPU
X
START
X
HW /
X
ERROR
NOINI
X
nnn.n
X
AUTnn
X
MANnn
X
oFL /
X
127.9
EXSTP
X
EX UP
X
204
Stands for variable numeric values
Error symbol
(slash): the texts on the left and right of the slash flash alternately
Operating mode
Manual
X
X
X
X
X
X
X
X
Meaning / cause
P-manual
Message after application
of electrical auxiliary pow-
er
Fault in the hardware
X
Positioner is not initialized
Actual position [in %] for
initialized positioner.
Flashing decimal point
shows communication with
a class-2 master
Automatic mode (nn =
setpoint)
Manual mode
(nn = setpoint)
Display range exceeded.
Possible causes:
Friction clutch or
transmission ratio
selector was disturbed
or
Positioner was in-
stalled on a different
actuator without being
reinitialized
Actuator was stopped with
the binary input
Actuator is moved to the
upper stop with binary
input
Operating Instructions, 09/2014, A5E00074631-12
Measure
Maintenance
Replace electron-
ics
Start initialization
Switch to auto-
matic mode with
mode button
Offset friction
clutch so that,
when the actuator
moves, the actual
value display
stays between 0.0
and 100.0, or
transmission ratio
selector, or
perform factory
settings (Preset)
and initialization
SIPART PS2 with and without HART