Certificates, Approvals, Explosion Protection - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Technical data

12.5 Certificates, approvals, explosion protection

12.5
Certificates, approvals, explosion protection
Certificates and approvals
Classification according to pressure
equipment directive (PED 97/23/EC)
CE conformity
Explosion protection
Explosion protection in accordance with
Flameproof enclosure encapsulation "d",
"XP"
Intrinsic safety "i", "IS"
Non-sparking "nA", "NI"
Dust, protection by means of enclosure
"t", "DIP"
For aluminum enclosure, narrow,
single-acting, without window
6DR5..1-.D...-..A.-Z...
For stainless steel enclosure
6DR5..2-.D...-..A.-Z...
For aluminum enclosure, with window
6DR5..3-.K...-..A.-Z...
Permissible ambient temperature
With and without HART
1)2)
6DR501. / 6DR502. / 6DR521. /
6DR522.
1)
6DR5.1 / 6DR5.25
1)
PROFIBUS PA or
FOUNDATION Fieldbus
6DR551. / 6DR552 / 6DR561. /
6DR562.
1)
6DR5515 / 6DR5525 / 6DR5615 /
6DR5625
1)
At ≤ -10 °C (+14 °F), the refresh rate of the display is limited. The following is valid for explosion-proof positioners:
1)
When using position feedback module, only T4 is permissible.
The following applies to fail in place: T4: -20 ... +60 °C (-4 ... +140 °F) as well as T6: -20 ... +50 °C (-4 ... +122 °F)
2)
246
For fluid group 1 gases; fulfills requirements according to article 3, paragraph
3 (good engineering practice SEP)
The applicable directives and applied standards with their revision levels can
be found in the EC declaration of conformity on the Internet.
Ex markings
ATEX/IECEx
II 2 G Ex d IIC T6/T4 Gb
II 2 G Ex ia IIC T6/T4 Gb
II 3 G Ex ic IIC T6/T4 Gc
II 2 D Ex ia IIIC T110°C Db
II 3 G Ex nA IIC T6/T4 Gc
II 2 D Ex tb IIIC T100°C Db
T4: -30 ... +80 °C (-22 ... +167 °F)
T6: -30 ... +50 °C (-22 ... +122 °F)
T4: -30 ... +80 °C (-22 ... +176 °F)
T6: -30 ... +50 °C (-22 ... +122 °F)
1)2)
T4: -20 ... +75 °C (-4 ... +167 °F)
T6: -20 ... +50 °C (-4 ... +122 °F)
T4: -30 ... +80 °C (-22 ... +176 °F)
T6: -30 ... +50 °C (-22 ... +122 °F)
FM/CSA
XP, Class I, Division 1, GP.ABCD
XP, Class I, Zone 1, AEx d, IIC, T6/T4
IS / I, II, III / 1 / A-G
IS / 1 / AEx / Ex ib / IIC, Gb
IS / 21 / AEx / Ex ib / IIIC, Db, T110°C
NI / I / 2 / A-D
NI / 2 / AEx / Ex nA, Ex ic / IIC, Gc
DIP / II, III / 1 / E-G
DIP / 21 / AEx / Ex tb / IIIC, Db,
T100°C
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12

Advertisement

Table of Contents
loading

This manual is also suitable for:

6dr53 series6dr51 series6dr52 seriesSipart ps2

Table of Contents