Diagnostics; Display Of Diagnostics Values - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Message
Line
Abov
Below Automatic
e
EXDWN
X
EXTPSt
InPSt
FST
X
SRT
X
MSRT
X
VPT
X
LEAKR
X
10.2

Diagnostics

10.2.1

Display of diagnostics values

Structure of the diagnostics display
The display in "Diagnostics" mode has a structure similar to that in "Configuration" mode:
● The upper line shows the value of the diagnostics variable.
● The lower line shows the number and the abbreviation of the displayed variable.
Some diagnostics value can be greater than 99999. In such a case, the display switches
over to the exponential view. Example: The value "1234567" is shown as "1.23E6".
General procedure
1. Press all three buttons at the same time for at least 2 seconds. You are now in the
diagnostics display.
2. Use the
3. Press the
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
Operating mode
Manual
X
X
X
X
X
X
button to select the next diagnostics value.
button for at least 2 seconds in order to exit the diagnostics display.
Meaning / cause
P-manual
Actuator is moved to the
lower stop with binary
input
The partial stroke test was
activated, e.g. using a
binary input
Cyclic partial stroke test
Full stroke test running
Step response test run-
ning
Multi-step response test
running
Valve performance test
running
A leakage test started by
communication is running
Alarm, error, and system messages
10.2 Diagnostics
Measure
205