Device; Management; Sensor Hub - Delta EnviroStation EMS2000 User Manual

Infrasuite ems
Table of Contents

Advertisement

5.2 Device

5.2.1. Management

The InsightPower SNMP IPv6 for EnviroStation Web allows detailed configurations
for Sensor HUB, Digital Input, Analog Input, Relay Output, Delta Bus, RS485,
Protocol, PDU, IPMI Device, IPMI Template and Reaction.
 Sensor HUB
 NO/ NC: Stands for Normal Open and Normal Close. If Normal Open is
selected, an event is triggered when 1. Dry Contact is closed or 2. Wet
Contact is provided with 5~24Vdc. If Normal Close is selected, an event is
triggered when 1. Dry Contact is open, or 2. Wet Contact is provided with
<1.5Vdc. Please see the following table:
Digital Value
1
0
Chapter 5 : InsightPower SNMP IPv6 for EnviroStation Web
Dry Contact
Close
Open
42
Wet Contact
5~24Vdc
< 1.5Vdc