RAMSES
718 P/S
No.
Object
name
Channel I1.1
30
switching
5.1.4 Important parameter settings
Standard or customer-defined parameter settings apply to unlisted parameters.
RAMSES 718 P/S:
Parameter page
RTC setting
Operating Mode
Channel I1
Switch object 1
PlanoSpot 360 KNX:
Parameter page
General
Channel C4 – presence
Only RAMSES 718 P
25
Only RAMSES 718 P
26
RAMSES 718 P / RAMSES 718 S
RAMSES
718 P/S
No.
Comment
Object
name
The windows status is detected at input E1 (window
Window
contact) and sent to the controller (window status) via
45
status
a group address. When opening the window, the
controller changes into frost protection mode.
Parameter
Control
Rotary control function
25
Button function
26
Objects for determining the operating
mode
Type of presence sensor type
(presence obj.)
Activate channel
Channel function
Number of telegrams
Object type
Send if input = 1
Telegram
Send if input = 0
Telegram
Send cyclically
Response after restoration of the bus
supply
Parameter
Channel C4 – presence
Presence switch-on
delay
Presence time delay
Typical applications
Setting
Heating control only
Blocked
Blocked
New: Operating mode, presence,
window status
Presence detectors
ON
Switch
One telegram
Switching (1 bit)
yes
ON
yes
OFF
yes
update (immediately)
Setting
active
5 min
10 min
75