6.12.1
set point calculation
Base set point
limits
Base set point
1
2
1 Fixed base set point of object or rotary control (only RAMSES 718 P)
2 Max. and min. valid base set points
3 Manual set point offset
4 Change between heating and cooling: Automatically or via object
5 Selection of operating mode, by operator, object, switching program or scene.
6 The set point is increased in cooling mode by the amount of the dead zone
RAMSES 718 P / RAMSES 718 S
Heating/cooling
Manual set
Heating mode
point offset
+ / -
3
4
Cooling mode
+ Dead zone
6
Operating mode/scene
Comfort
- Standby
- Night
Frost protection
7
Comfort
5
+ Standby
+ Night
Heat protection
8
7
The set point is replaced by the set point for frost protection mode
8
The set point is replaced by the set point for heat protection mode
9
set point after reductions caused by the operating mode
10 set point after increases caused by the operating mode
11 The limits for frost and heat protection must be adhered to
12 Current set point after increases, reductions and limits caused by the operation
Appendix
9
Safety
limits
Current
set point
11
12
10
107