4.6.8 Cooling set points
Designation
Dead zone between heating and
cooling
Increase in standby mode
(during cooling)
Increase in night mode
(during cooling)
set point for heat protection
mode
(during cooling)
Only in 2 pipe system
19
Only in 2 pipe system
20
Only for type of control heating = 2 points.
21
Only with type of control cooling = 2-point.
22
RAMSES 718 P / RAMSES 718 S
The application programmes RAMSES 718 P/S
Values
0 K
, 0.5 K
, 1 K, 1.5 K,
19
20
2 K, 2.5 K, 3 K, 3.5 K
4 K, 4.5 K, 5 K, 5.5 K, 6 K
+ hysteresis heating
21
+ hysteresis cooling
22
0 K, 0.5 K, 1 K
1.5 K, 2 K, 2.5 K
3 K, 3.5 K, 4 K
4.5 K, 5 K
3 K, 4 K, 5 K
6 K, 7 K, 8 K
0 = 42 °C, i.e. no real
heat protection
29 °C, 30 °C, 31 °C
32 °C, 33 °C, 34 °C
35°C
Description
Specifies the buffer zone
between set points for heating
and cooling mode.
The dead zone is expanded
through hysteresis in switching
(2 point) control.
See in the Appendix: Dead zone
The standby temperature is
increased in cooling mode.
The in cooling mode, the
temperature is increased in night
mode.
Heat protection represents the
maximum permitted temperature
for the controlled room. It
performs the same function
during cooling as the frost
protection mode during heating,
e.g. saves energy while
prohibiting non-permitted
temperatures.