Theben KNX Series Handbook page 42

Table of Contents

Advertisement

Designation
When increasing the
temperature at the rotary
control
16
Time for comfort extension
Cyclical sending of current
operating mode
Exception: if a window is opened (window object = 1), the room temperature controller
15
switches to frost protection mode
Only RAMSES 718 P
16
RAMSES 718 P / RAMSES 718 S
The application programmes RAMSES 718 P/S
Values
Presence button
Do not set presence
object
Set presence object
30 min
1 h
1.5 h
2 h
2.5 h
3 h
3.5 h
do not send cyclically
every 2 min.
every 3 min.
...
every 45 min.
every 60 min.
Description
If a new operating mode is
received on the operating mode
preset object with the presence
object set, it will be accepted and
the presence object will be reset.
Reception of the same operating
mode prior to the presence
status (e.g. via cycl. sending) is
ignored.
If the presence object is set for
night/frost mode, it is reset after
running the parameterised
comfort extension
15
If the presence object is set
during standby mode, the
comfort operating mode is
accepted without time restriction.
Only if type of presence sensor =
presence button.
Only increase the temperature
Presence object is set, the
controller changes to comfort
mode.
This determines how long the
controller should remain in
comfort mode after the presence
button is pressed.
How often should it be resent?