4.7.2 Switch function I1, I2, I3, I4
Designation
Activate channel
Channel function
Debounce time
Connected push button
Long button push starting at
Time for double-click
Send cyclically
Number of telegrams
Activate block function
Block telegram
RAMSES 718 P / RAMSES 718 S
The application programmes RAMSES 718 P/S
Values
no
yes
Switch..
Push button..
Dimming..
Blinds..
30 ms, 50 ms, 80 ms
100 ms, 200 ms,
1 s , 5 s, 10 s
NO contact
Opening contact
300 ms, 400 ms
500 ms, 600 ms
700 ms, 800 ms
900 ms, 1 s
300 ms, 400 ms
500 ms, 600 ms
700 ms, 800 ms
900 ms, 1 s
every min
every 2 min.
every 3 min.
...
every 30 min.
every 45 min.
every 60 min.
one telegram
two telegrams
three telegrams
no
yes
Block with 1 (standard)
Block with 0
Description
Use input?
A push button is connected to
the input.
In order to avoid a disruptive
switching due to debouncing of
the contact connected to the
input, the new status of the input
is only accepted after a delay
time.
Larger values (≥ 1s) can be used
as a switch-on delay.
Set the Type of connected
contact.
Serves to clearly differentiate
between long and short button
push.
If the push button is pressed for
at least as long as the set time,
then a long button push will be
registered.
Serves to differentiate between a
double-click and 2 single clicks.
Time period in which the second
click must begin, in order to
recognise a double-click.
Common cycle time for all 3
initial objects of the channel.
Each channel has 3 initial objects
and can thus send up to 3
different telegrams.
No block function.
Show block function parameter
page.
0 = enable
1 = block
0 = block
1 = enable