Theben KNX Series Handbook page 68

Table of Contents

Advertisement

4.7.4.2 Double-click parameter page
Designation
Object type
Telegram
Send cyclically
Response after
restoration of the bus
RAMSES 718 P / RAMSES 718 S
Values
Switching (1 bit)
Priority (2 bit)
Value 0-255
Percentage value (1 byte)
2 byte floating-point number
DPT 9.x
4 byte floating-point number
DPT 14.x
With object type = switching 1
bit
ON
OFF
BY
With object type = priority 2 bit
inactive
ON
OFF
With object type = value 0-255
0-255
With object type = percentage
value
1 byte
0-100%
With object type = 2 byte
floating-point number
-670760...670760
Std.: 0
With object type = 4 byte
floating-point number
-1E+38.. 1E+38
Std.: 0
do not send cyclically
every min
every 2 min.
every 3 min.
...
every 45 min.
every 60 min.
none
The application programmes RAMSES 718 P/S
Description
Telegram type for this object.
Send switch-on command
Send switch-off command
Invert current state (ON-OFF-ON
etc.)
Function
Priority not active
(no control)
Priority ON
Priority ON (control:
enable, on)
Priority OFF
(control: disable, off)
Any value between 0 and 255
can be sent.
Any percentage value between 0
and 100 % can be sent.
Any value between -670760 and
670760 can be sent.
Any value between -1E+38 and
1E+38 can be sent.
Input format: The ETS only allows
the input as a decimal without
power.
Example: 15234825.123456
How often should it be resent?
Do not send.
Value
0 (00
)
bin
3 (11
)
bin
2 (10
)
bin
68