Theben KNX Series Handbook page 66

Table of Contents

Advertisement

4.7.4 Blinds function I1, I2, I3, I4
Designation
Activate channel
Channel function
Debounce time
Long button push starting at
Double-click additional function
Time for double-click
Activate block function
Block telegram
RAMSES 718 P / RAMSES 718 S
The application programmes RAMSES 718 P/S
Values
no
yes
Switch..
Push button..
Dimming..
Blinds..
30 ms, 50 ms, 80 ms
100 ms, 200 ms,
1 s , 5 s, 10 s
300 ms, 400 ms
500 ms, 600 ms
700 ms, 800 ms
900 ms, 1 s
no
yes
300 ms, 400 ms
500 ms, 600 ms
700 ms, 800 ms
900 ms, 1 s
no
yes
Block with 1 (standard)
Block with 0
Description
Use input?
The input controls a blinds
actuator.
In order to avoid a disruptive
switching due to debouncing of
the contact connected to the
input, the new status of the input
is only accepted after a delay
time.
Larger values (≥ 1s) can be used
as a switch-on delay
Serves to clearly differentiate
between long and short button
push.
If the push button is pressed for
at least as long as the set time,
then a long button push will be
registered.
No double-click function
The double-click parameter page
is shown.
Serves to differentiate between a
double-click and 2 single clicks.
Time period in which the second
click must begin, in order to
recognise a double-click.
No block function.
Show block function parameter
page.
0 = enable
1 = block
0 = block
1 = enable
66

Advertisement

Table of Contents
loading

Related Products for Theben KNX Series

This manual is also suitable for:

Ramses 718 pRamses 718 s

Table of Contents