Profile 16 - Siemens SITRANS F US Protocol Manual

Clamp-on ultrasonic flowmeters
Hide thumbs Also See for SITRANS F US:
Table of Contents

Advertisement

A.1.17

Profile 16

Data Description
Modbus
Reg
Site ID
30501
Date: Year
30101
Date: Month
30102
Date: Day
30103
Time: Hour
30104
Time: Minute
30105
Time: Second
30106
C1 Inst.Flow
30109
Rate
C1 Flow Rate
30517
Units
C2 Inst.Flow
30111
Rate
C2 Flow Rate
30521
Units
C3 Inst.Flow
30113
Rate
C3 Avg Flow
30125
Rate
C3 Flow Rate
30525
Units
C1 Total
30145
C1 Total Units
30557
C2 Total
30147
C2 Total Units
30561
C3 Total
30149
C3 Total Units
30565
C1 Sonic Vel
30157
C2 Sonic Vel
30159
Sonic Vel Units
30577
C1 Status
10021
/Alarms: Spacing
C1 Status
10022
/Alarms: Empty
C1 Status
10023
/Alarms: Rate
C1 Status
10024
/Alarms: Fault
C1 Status
10025
/Alarms: Aeration
C1 Status
10026
/Alarms: Memory
F US Clamp-on Communications Protocol Manual
Hardware Installation Manual, 11/2015, A5E34981613-AC
Profile 16 (FUS1010-5N04-5.04.05-1-2CO)
Ethernet/IP
Bytes
Type
Tag Name
8
String
String_In
2
Integer
Analog_In
2
Integer
Analog_In
2
Integer
Analog_In
2
Integer
Analog_In
2
Integer
Analog_In
2
Integer
Analog_In
4
Real
Analog_In
8
String
String_In
4
Real
Analog_In
8
String
String_In
4
Real
Analog_In
4
Real
Analog_In
8
String
String_In
4
Real
Analog_In
8
String
String_In
4
Real
Analog_In
8
String
String_In
4
Real
Analog_In
8
String
String_In
4
Real
Analog_In
4
Real
Analog_In
8
String
String_In
1 Bit
Coil
Binary_In
1 Bit
Coil
Binary_In
1 Bit
Coil
Binary_In
1 Bit
Coil
Binary_In
1 Bit
Coil
Binary_In
1 Bit
Coil
Binary_In
A.1 Modbus, EIP, HART & N2 Profile Mappings
HART
OS Format
CMD VAR
0
UINT16
n/a
0
Float
n/a
1
Float
n/a
2
Float
n/a
3
Float
n/a
4
Float
n/a
5
Float
n/a
6
Float
129
6-06h T
4
UINT16
131
6-06h
7
Float
129
7-07h Q
8
UINT16
131
7-07h
8
Float
129
8-08h
9
Float
129
3-03h P
12
UINT16
131
3-03h
10
Float
129
34-22h
16
UINT16
131
34-22h
11
Float
129
35-23h
20
UINT16
131
35-23h
12
Float
129
36-24h S
24
UINT16
131
36-24h
13
Float
n/a
14
Float
n/a
28
UINT16
n/a
0
UINT16
n/a
0
UINT16
n/a
0
UINT16
n/a
0
UINT16
n/a
0
UINT16
n/a
0
UINT16
n/a
Appendix A
N2
Type
Ad Sz
BD(Byte)
1
8
ADI(Int)
1
1
ADI(Int)
2
1
ADI(Int)
3
1
ADI(Int)
4
1
ADI(Int)
5
1
ADI(Int)
6
1
ADF(Float)
1
1
BD(Byte)
9
8
ADF(Float)
2
1
BD(Byte)
17 8
ADF(Float)
3
1
ADF(Float)
4
1
BD(Byte)
25 8
ADF(Float)
5
1
BD(Byte)
33 8
ADF(Float)
6
1
BD(Byte)
41 8
ADF(Float)
7
1
BD(Byte)
49 8
ADF(Float)
8
1
ADF(Float)
9
1
BD(Byte)
57 8
DI(Dig In)
1
1
DI(Dig In)
3
1
DI(Dig In)
4
1
DI(Dig In)
5
1
DI(Dig In)
6
1
DI(Dig In)
7
1
95