Profile 1 - Siemens SITRANS F US Protocol Manual

Clamp-on ultrasonic flowmeters
Hide thumbs Also See for SITRANS F US:
Table of Contents

Advertisement

Appendix A
A.1 Modbus, EIP, HART & N2 Profile Mappings
A.1.2

Profile 1

Data Description
Modbus
Reg
Site ID
30501
Date: Year
30101
Date: Month
30102
Date: Day
30103
Time: Hour
30104
Time: Minute
30105
Time: Second
30106
Inst.Flow Rate
30107
Avg Flow Rate
30119
Flow Rate Units
30517
Raw Flow
30131
Raw Flow Units
30537
Total
30143
Total Units
30557
Sonic Vel
30155
Sonic Vel Units
30577
Signal Strength
30165
Sig Strength Units
30593
Aeration
30171
Aeration Units
30609
Status/Alarms:
10001
Spacing
Status/Alarms:
10002
Empty
Status/Alarms:
10003
Rate
Status/Alarms:
10004
Fault
Status/Alarms:
10005
Aeration
Status/Alarms:
10006
Memory
Status/Alarms:
10007
Makeup
Status/Alarms:
10008
Interface
Status/Alarms:
10010
Zeromatic
Delta Time
30177
Delta Time Units
30629
68
Profile 1 (FUS1010-5N01-5.04.05-1CO)
Ethernet/IP
Bytes
Type
Tag Name OS Format
8
String
String_In
2
Integer
Analog_In
2
Integer
Analog_In
2
Integer
Analog_In
2
Integer
Analog_In
2
Integer
Analog_In
2
Integer
Analog_In
4
Real
Analog_In
4
Real
Analog_In
8
String
String_In
4
Real
Analog_In
8
String
String_In
4
Real
Analog_In
8
String
String_In
4
Real
Analog_In
8
String
String_In
2
Integer
Analog_In
8
String
String_In
2
Integer
Analog_In
8
String
String_In
1 Bit
Coil
Binary_In
1 Bit
Coil
Binary_In
1 Bit
Coil
Binary_In
1 Bit
Coil
Binary_In
1 Bit
Coil
Binary_In
1 Bit
Coil
Binary_In
1 Bit
Coil
Binary_In
1 Bit
Coil
Binary_In
1 Bit
Coil
Binary_In
4
Real
Analog_In
8
String
String_In
HART
CMD VAR
0
UINT16
n/a
0
Float
n/a
1
Float
n/a
2
Float
n/a
3
Float
n/a
4
Float
n/a
5
Float
n/a
6
Float
n/a
7
Float
129
0-00h P
4
UINT16
131
0-00h
6
Float
n/a
8
UINT16
n/a
9
Float
129
33-21h S
12
UINT16
131
33-21h
10
Float
n/a
16
UINT16
n/a
11
Float
n/a
20
UINT16
n/a
12
Float
n/a
24
UINT16
n/a
0
UINT16
n/a
0
UINT16
n/a
0
UINT16
n/a
0
UINT16
n/a
0
UINT16
n/a
0
UINT16
n/a
0
UINT16
n/a
0
UINT16
n/a
0
UINT16
n/a
13
Float
n/a
28
UINT16
n/a
F US Clamp-on Communications Protocol Manual
Hardware Installation Manual, 11/2015, A5E34981613-AC
N2
Type
Ad
Sz
BD(Byte)
1
8
ADI(Int)
1
1
ADI(Int)
2
1
ADI(Int)
3
1
ADI(Int)
4
1
ADI(Int)
5
1
ADI(Int)
6
1
ADF(Float)
1
1
ADF(Float)
2
1
BD(Byte)
9
8
ADF(Float)
3
1
BD(Byte)
17
8
ADF(Float)
4
1
BD(Byte)
25
8
ADF(Float)
5
1
BD(Byte)
33
8
ADF(Float)
6
1
BD(Byte)
41
8
ADF(Float)
7
1
BD(Byte)
57
8
DI(Dig In)
1
1
DI(Dig In)
3
1
DI(Dig In)
4
1
DI(Dig In)
5
1
DI(Dig In)
6
1
DI(Dig In)
7
1
DI(Dig In)
8
1
DI(Dig In)
9
1
DI(Dig In)
2
1
ADF(Float)
8
1
BD(Byte)
49
8

Advertisement

Table of Contents
loading

Table of Contents