Table 4- 9 Command 9 - Read Device Variable With Status; Table 4- 10 Command 11 - Read Unique Identifier Associated With Tag - Siemens SITRANS F US Protocol Manual

Clamp-on ultrasonic flowmeters
Hide thumbs Also See for SITRANS F US:
Table of Contents

Advertisement

HART Communications
4.1 Universal HART Commands
Table 4- 9
Description
Extended Field Device Status
Slot 0: Device Variable Code
Slot 0: Device Variable Classification
Slot 0: Device Variable Units Code
Slot 0: Device Variable Value
Slot 0: Device Variable Status
Slot 1: Device Variable Code
Slot 1: Device Variable Classification
Slot 1: Device Variable Units Code
Slot 1: Device Variable Value
Slot 1: Device Variable Status
Slot 2: Device Variable Code
Slot 2: Device Variable Classification
Slot 2: Device Variable Units Code
Slot 2: Device Variable Value
Slot 2: Device Variable Status
Slot 3: Device Variable Code
Slot 3: Device Variable Classification
Slot 3: Device Variable Units Code
Slot 3: Device Variable Value
Slot 3: Device Variable Status
Slot 0 data time stamp
Table 4- 10
Description
"254"
Device Type
Minimum number of Preambles
HART Protocol Major Revision Number
Device Revision Level
Software Revision Level
Hardware Revision Level
Physical Signaling Code
Flags
Device ID
Minimum number of preambles
Maximum number of Device Variables
Configuration Change Counter
Extended Field Device Status
Manufacturer Identification Code
Private Label Distribution Code
Device Profile
40
Command 9 - Read Device Variable with Status
Command 11 - Read Unique identifier Associated with Tag
Byte
Format
Comments/Value
<refer to common table 17>
0
Bits
246 <Primary Variable>
1
U-8
0-not classified
2
Enum
< write units CMD 35 or 44>
3
Enum
4-7
Float
8
Bits
<Device Status Common Table>
247 <Secondary Variable>
9
U-8
0-not classified
10
Enum
11
Enum
<select SV Units CMD 161>
12-15
Float
16
Bits
<Device Status Common Table>
248 <Tertiary Variable>
17
U-8
0-not classified
18
Enum
19
Enum
<select TV Units CMD 163>
20-23
Float
24
Bits
<Device Status Common Table>
249 <Quaternary Variable>
25
U-8
0-not classified
26
Enum
27
Enum
<select QV Units CMD 165>
28-31
Float
32
Bits
<Device Status Common Table>
33-36
Time
Byte
Response
Comments/Value
0
FE
1-2
2A04
Siemens FUS
3
5
4
7
5
6
<5 most significant bits>
7
<3 least significant bits>
7
0
A5E31571875A
8
See Common table 11
<unique ID for each >
9-11
12
13
<increments with each write>
14-15
See Common table 17
16
17-18
002A
Siemens
19-20
002A
Siemens
21
01
Process Automation Device
F US Clamp-on Communications Protocol Manual