Troubleshooting; Errors When Start/Stop Operation Was Executed Using Fpwin Gr7 - Panasonic FP0H User Manual

Programmable controller control unit
Hide thumbs Also See for FP0H:
Table of Contents

Advertisement

Logging/Trace

Troubleshooting

6.2 Troubleshooting

6.2.1 Errors When Start/Stop Operation was Executed Using FPWIN GR7

This section describes the messages displayed when the start or stop operation is performed
on the "Logging/Trace Monitor" dialog box, and countermeasures.
 List of error messages
Error message
60 From PLC:
Application error
- Parameter error
62 From PLC:
Application error
- Registration error
78 From PLC:
Application error
- No SD error
90 From PLC:
Application error
- Logging error
6-4
Situation
Any box of LOG number is not
checked.
An unregistered LOG number was
activated.
No SD memory card is inserted, or
the battery cover is open.
An attempt was made to download
logging setting parameters during
logging operation.
An attempt was made to display
data on a time chart during trace
operation.
Countermeasures
Check the box of the LOG number to be
started.
Check if the settings matches the LOG
number to be activated.
Check if an SD memory card is inserted,
and close the battery cover.
Depending on the situation, wait for the
completion of logging operation, or
download the setting parameters again
after performing the logging stop operation.
Depending on the situation, wait for the
completion of trace operation, or press the
[Time Chart] button after performing the
trace stop operation.