7.6.5
Requesting an echo profile
Procedure
After commissioning the device, an echo profile may be viewed on the HMI or using a remote
engineering system, such as SIMATIC PDM.
For details, see SIMATIC PDM (Page 207).
①
②
③
④
See Confidence (Page 202)
1)
See Auto false echo suppression and Custom TVT (Page 202)
2)
3)
Where AFES has been learned, AFES curve replaces TVT curve (see Auto false echo suppression
(Page 98) ).
1. In measurement view, press
Diagnostics
2. Press
3. To update to current profile, press
4. To exit and return to the previous menu, press
7.6.6
Device address
Setting a device address is not necessary for local operation, but must be set if configuring the
device for use on a HART network. See Polling address (4.1) (Page 145).
SITRANS LR500 series with mA/HART
Operating Instructions, 03/2024, A5E51099898-AA
X-axis: Distance
Distance units can be set to: m, cm,
mm, ft, in.
Y-axis: Echo amplitude (in dB)
Distance from sensor face to target
Echo confidence
1)
Echo profile (3.2.1) (Page 130).
to start wizard and request a profile.
⑤
Algorithm used
⑥
Echo
⑦
TVT
3)
to navigate to parameter view Maint. and diag.
and
button.
Commissioning
7.6 Local commissioning
2)
83