Digital Ready Unit Mounted
Temperature Sensor Specifications
A 10 K ohm Negative Temperature Coefficient (NTC)
sensor and a 1 K ohm Positive Temperature Coefficient
sensor is provided for the discharge air, outdoor air and
room air temperature measurement. They are located
next to each other in the air stream as shown in
113. Each is wired to the terminal strip separately so that
the Automatic Temperature Control contractor may select
the appropriate sensor for the application.
10 K ohm NTC Sensor
The 10 K ohm NTC sensor is constructed from stainless
steel with an epoxy seal and twisted wire leads.
Type:
10K ohm @ 25°C
Accuracy:
±0.2°F, 40°F - 80°F
±0.36°F, 32°F - 158°F
1 K ohm PTC Sensor
The 1 K ohm sensor is a shrink-wrap encapsulated, PTC
silicon sensing element with stranded, tinned copper
wire leads (#22 AWG).
Type:
1035 ohm @ 25°C
Accuracy:
±0.9°F, 5°F - 167°F
Table 38: Temperature Sensors Resistance Values
Temperature (°C)
10 K ohm (NTC)
Resistance (ohms)
Temperature (°C)
1 K ohm (PTC)
Resistance (ohms)
IM 817-7
Figure 113: Sensor Locations
Figure
-40
-20
0
337200
97130
32660
-40
-20
0
613
727
855
54
Discharge Air Sensor
Room Air Sensor
Holes in Front
Access Panel
Outdoor Air
Opening
Outdoor Air Sensors
20
25
30
12490
10000
8056
20
25
30
997
1035
1074
40
50
60
5326
3602
2489
40
50
60
1153
1237
1323
www.DaikinApplied.com