Digital Ready Unit Mounted Temperature Sensor Specifications; Digital Ready-Damper Actuator Specifications; Outdoor Air/Return Air Damper Actuator; Face & Bypass Damper Actuator - Daikin AVS Installation Manual

Classroom unit ventilators
Table of Contents

Advertisement

Digital Ready Unit Mounted
Temperature Sensor Specifications
A 10 K ohm Negative Temperature Coefficient (NTC) sensor and a
1 K ohm Positive Temperature Coefficient sensor is provided for the
discharge air, outdoor air and room air temperature measurement. They
are located next to each other in the air stream as shown in Figure 114.
Each is wired to the terminal strip separately so that the Automatic
Temperature Control contractor may select the appropriate sensor for
the application.
10 K ohm NTC Sensor
The 10 K ohm NTC sensor is constructed from stainless steel with an
epoxy seal and twisted wire leads.
10K ohm @ 25ºC
Type:
±0.2ºF, 40
Accuracy:
±0.36ºF, 32ºF - 158ºF
1 K ohm PTC Sensor
The 1 K ohm sensor is a shrink-wrap encapsulated, PTC silicon sensing
element with stranded, tinned copper wire leads (#22 AWG).
1035 ohm @ 25ºC
Type:
±0.9ºF, 5ºF - 167ºF
Accuracy:
Table 26 - Temperature Sensors Resistance Values
Temperature (ºC)
10 K ohm (NTC)
Resistance (ohms)
Temperature (ºC)
1 K ohm (PTC)
Resistance (ohms)
Digital Ready – Damper Actuator
Specifications

Outdoor Air/Return Air Damper Actuator

The outdoor air/return air damper actuator is a unit mounted, direct
coupled, proportional control actuator that spring returns the outdoor
air damper shut upon a loss of power. The actuator provides proportional
damper control based on a 2 to 10 VDC input from the DDC Unit
Ventilator Controller (UVC). A 4 to 20 mA input signal can be used with
the field addition of a Belimo ZG-R01 (or equivalent) 500 ohm resistor
(by others). Refer to the wiring diagram for proper installation of the
resistor. A 2 to 10 VDC output signal is provided for damper position
feedback. Rotation is clockwise to open OA, close RA.
Face and Bypass Damper Actuator
The Face & Bypass damper actuator is a unit mounted, direct coupled,
non-spring returned actuator used for the modulation of the face and
bypass damper. The actuator provides proportional damper control
Table 27. - Actuators Technical Data
Actuator Type
Outdoor Air/Return Air
Damper Actuator
Face & Bypass
Damper Actuator
Page 44 of 60
F - 80ºF
o
-40
337200
97130
-40
613
727
Power
Power
Supply
Consumption
24 VAC ±20%
50/60 HZ
2 Watts
24 VDC ±10%
24 VAC ±20%
Running: 2.5 Watt;
50/60 HZ
Holding: 1 Watt
24 VDC ±10%
Figure 114 - Sensor Locations
Outdoor Air
Opening
Outdoor Air Sensors
-20
0
20
32660
12490
10000
-20
0
20
855
997
based on a 2 to 10 VDC input from the DDC Unit Ventilator Controller
(UVC). A 4 to 20 mA input signal can be used with the field addition of
a Belimo ZG-R01 (or equivalent) 500 ohm resistor (by others). Refer to
the wiring diagram for proper installation of the resistor. A 2 to 10 VDC
output signal is provided for damper position feedback. The gears can
be manually disengaged with a button on the actuator cover. Rotation
is counterclockwise to bypass air around coil.
Figure 115 - Outdoor Air/Return Air Damper Actuator & Face
and Bypass Damper Actuator
Transformer
Torque
Sizing
4 VA
(class 2 power source)
45 in-lb
5 VA
(class 2 power source)
45 in-lb
Discharge Air Sensor
Room Air Sensor
Holes in Front
Access Panel
25
30
40
8056
5326
25
30
40
1035
1074
1153
Running
Time
80 to 110 sec
Reversible with built in switch L/R
for 0 to 35 in-lb
L = CW with an increase in voltage.
R = CCW with an increase in voltage.
Spring: reversible with CW/CCW
90 sec constant
mounting.
(independent
Motor: reversible with built in switch.
of load)
CW = CW with a decrease in signal.
CCW = CCW with a decrease in signal.
50
60
3602
2489
50
60
1237
1323
Direction of Rotation
IM 817-4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

AvvAvbAvr

Table of Contents