Daikin AVV Installation And Maintenance Manual page 28

Classroom unit ventilators floor models digital ready, microtec control (“j” vintage) field controls by others
Hide thumbs Also See for AVV:
Table of Contents

Advertisement

3-Way Modulating Valve (Chilled Water, Hot
Water or Combination)
Three-way modulating control valves for MicroTech are
designed to regulate the flow of hot or chilled water or
the combination. They consist of a nickel plated brass
body and stem with chrome plated brass ball valve, with
a spring return, proportional actuator. The optional valve
accessory is shipped separate from the unit ventilator
for field installation to prevent shipping damage and to
provide flexibility in making the field piping connection.
Figure 75: 3-Way Modulating Valve (Chilled Water, Hot
Water or Combination) Dimensions
D
AB
B
E
F
Table 26: 3-Way Modulating Valve 1/2" – Dimensions
Valve Part No .
Cv
B309(B)
0.8
B310(B)
1.2
B311(B)
1.9
B312(B)
3.0
B313(B)
4.7
B318(B)
7.4
Table 27: Modulating 3-Way Hot Water, Chilled Water or 2-Pipe CW/HW Valve 1/2" – Pressure Drop
Cv
3-Way CCV Part
Maximum
No .
Rating
B309(B)
0.8
B310(B)
1.2
B311(B)
1.9
B312(B)
3.0
B313(B)
4.7
B318(B)
7.4
IM 817-7
A
A
Connection Size
A
(inches)
6.59" (167mm)
1/2"
6.59" (167mm)
Connection
1 PSI
2 PSI
Size
0.8
1.
1.2
1.7
1.9
2.7
1/2"
3.0
4.2
4.7
6.6
7.4
10
Table 24: 3-Way Actuator Specifications (CW, HW, CW/HW)
Power Supply
Electrical Connection
Overload Protection
Operating Range Y
Input Impedance
Feedback Output U
Angle of Rotation
Position Indication
Running Time (Motor)
Running Time (Fail-Safe)
Ambient Humidity
Ambient Temperature Range
Storage Temperature Range
Table 25: 3-Way Valve Body Specifications (CW, HW, CW/HW)
Service
Flow Characteristic
Controllable Flow Range
Body Pressure Rating [psi]
Media Temperature Range
C
(Water)
Max Differential Pressure
(Water)
Close-Off Pressure
B
C
2.38" (60mm)
4.9" (124mm)
2.38" (60mm)
4.9" (124mm)
2.73" (69mm)
5.5" (140mm)
Pressure Drop Across the Valve
3 PSI
4 PSI
5 PSI
1.4
1.6
1.8
2.
2.4
2.8
3.3
3.8
4.2
5.2
6.0
6.8
8.1
9.4
11
13
15
17
28
24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10%
3ft [1m], 18 GA plenum cable with 1/2"
conduit connector
electronic throughout 0° to 95° rotation
2 to 10 VDC, 4 to 20 mA w/ ZG-R01 (500
Ω, 1/4 W resistor)
100 k Ω for 2 to 10 VDC (0.1 mA), 500 Ω
for 4 to 20 mA
2 to 10 VDC, 0.5 mA max
Max. 95°, 90°
visual indicator, 0° to 95° (0° is full spring
return position)
95 sec
<25 sec
max. 95% RH non-condensing
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
chilled, hot water, up to 60% glycol
A-port Equal percentage; B-port modified
linear for constant flow
75°
600
0°F to 250°F [-18°C to 120°C]
50 psi (345 kPa)
200 psi
D
E
4.32" (110mm)
1.53" (38mm)
4.71" (120mm)
1.53" (38mm)
4.8" (122mm)
1.53" (38mm)
6 PSI
7 PSI
8 PSI
9 PSI
2.0
2.
2.3
2.9
3.2
3.4
4.7
5.0
5.4
7.3
7.9
8.5
12
12
13
18
20
21
www.DaikinApplied.com
F
1.2" (31mm)
1.29" (33mm)
1.47" (37mm)
10 PSI
2.4
2.5
3.6
3.8
5.7
6.0
9.0
9.5
14
15
22
23