Daikin AVV Installation And Maintenance Manual page 50

Classroom unit ventilators floor models digital ready, microtec control (“j” vintage) field controls by others
Hide thumbs Also See for AVV:
Table of Contents

Advertisement

Table 37: Unit Ventilator MicroTech board to room temperature sensor wiring
Terminal Block Label
TB1
Sensor 910247458
Sensor 910247448
Sensor 910247453
Sensor 910247450
Description
24VAC
Wire
908
Typical Wiring
Terminal Label
R
Description
24VAC
Terminal Designations
● = Active Terminal
○ = Not Used
IM 817-7
MicroTech Base Board
H6-1
H6-2
Shutdown
Occupancy
Status LED
(Not Used)
907
906
U
1 (ST)
Unit Status
Unoccupied
Setpoint Adjust
Output
Room Temperature Sensor
H6-3
H6-4
H6-5
Setpoint
Unit Mode
909
912
901
3 (SP)
2 (FM)
Unit Mode
50
H6-6
H6-7
Fan Speed
10K RTD
902
911
6 (FC)
4 (UTS)
Room Temp
Fan Speed
Sensor &
Tenant Override
www.DaikinApplied.com
H6-8
Ground
910
5 (GND)
Ground