Table 43: High Static Applications Electric Heat Capacities, Amps, Wire Sizing, and Over Current Protection
Number of Electric Elements
KW
MBH
Final Air Temp F (70 F entering air temp)
Air Temperature Rise
Electric Heating Amperes
208-60-1
Unit Minimum Circuit Ampacity
Maximum Fuse Size or Circuit Breaker Amps
Electric Heating Amperes
230-60-1
Unit Minimum Circuit Ampacity
Maximum Fuse Size or Circuit Breaker Amps
Electric Heating Amperes
265-60-1
Unit Minimum Circuit Ampacity
Maximum Fuse Size or Circuit Breaker Amps
Electric Heating Amperes
208-60-3
Unit Minimum Circuit Ampacity
Maximum Fuse Size or Circuit Breaker Amps
Electric Heating Amperes
230-60-3
Unit Minimum Circuit Ampacity
Maximum Fuse Size or Circuit Breaker Amps
Electric Heating Amperes
460-60-3
Unit Minimum Circuit Ampacity
Maximum Fuse Size or Circuit Breaker Amps
Note:
Electric heat disconnect provided.Cabinets
IM 817-7
AVS AVV
Unit Type
AVS AVV
AVV AVR
AVR
AVR
3
6
3
6
12
8
20.48
40.96
27.30
95.20
120.30
95.20
25.20
50.30
25.20
28.80
57.70
38.50
42.20
78.33
54.33
45
80
55
25.04
50.09
33.18
37.50
68.81
47.68
40
70
50
21.74
43.59
28.85
33.38
60.69
42.26
35
70
45
16.70
33.30
22.20
27.08
47.83
33.95
30
50
35
14.50
28.90
19.20
24.33
42.33
30.20
25
45
35
7.20
14.50
9.60
15.20
24.33
18.20
20
25
20
66
AVS AVV
AVV AVR
AVV AVR
AVR
6
3
6
16
10
20
54.61
34.13
68.26
120.30
95.20
120.30
50.30
25.20
50.30
76.90
48.10
96.20
102.33
66.33
126.45
110
70
130
66.37
41.63
83.27
89.16
58.24
110.29
90
60
120
57.70
36.17
72.33
78.32
51.41
96.62
80
55
100
44.40
27.80
55.50
61.70
40.95
75.58
70
45
80
38.30
24.00
48.10
54.07
36.20
66.33
55
40
70
19.20
12.00
24.00
30.20
21.20
36.20
35
25
40
www.DaikinApplied.com
AVS AVV
AVV AVR
AVR
3
6
12
24
40.96
81.91
95.20
120.30
25.20
50.30
57.70
115.40
78.33
150.45
80
175
50.09
100.17
68.81
131.42
70
140
43.59
87.07
60.69
115.04
70
120
33.30
66.60
47.83
89.45
50
90
28.90
57.81
42.33
78.46
45
80
14.50
28.90
24.33
42.33
25
45