Typical Steam Coil Piping - Daikin AVV Installation And Maintenance Manual

Classroom unit ventilators floor models digital ready, microtec control (“j” vintage) field controls by others
Hide thumbs Also See for AVV:
Table of Contents

Advertisement

For steam applications, the 2-way, angle pattern valve
furnished is normally piped open to the coil. All steam
coils are 1-1/8" (34mm) female sweat connections. Coil
connections terminate 9" (229mm) from the end of the unit.
Steam coils have a factory-installed pressure equalizing
valve and a 24" (610mm) long pressure equalizing line
that terminates in a 1/2" M.P.T. fitting.
Steam connections may be same end as cooling coil
connections, but are recommended to be opposite end
to facilitate piping. When using MicroTech controls, they
must be opposite end.
See
Figure 83
through
Figure 87 on page
Connect the 1/4" (6.35mm) vacuum breaker tube to
the downstream return line. Make this connection
downstream of the trap outlet.
Figure 85: Opposite End Drain Connection – (78/79 Coils)
Left End View
Note:
Left Hand Steam Supply and Right Hand Steam Return (Shown)

Typical Steam Coil Piping

Figure 86: Face and Bypass With 2-Way End-of-Cycle
Valve - Same End Drain Connection (Piping Within Unit
End Compartment)
9
8
4
7
www.DaikinApplied.com
33.
Right End View
13
15
14
6
Figure 87: Face and Bypass With 2-Way End-of-Cycle
Valve - Same End Drain Connection (Piping Outside Unit
End Compartment)
15
4
6
Table 30: Number Descriptions for
Three-way End of Cycle control valve (Daikin)
1
Coil air vent (Daikin)
2
Coil drain (Daikin)
3
Shutoff valve (by others)
4
Balancing shutoff valve(s) (by others)
5
Supply
6
Return
7
Unions (by others), must disconnect below floor line
8
Two-way, End of Cycle two-position valve (Daikin)
9
Union: Half attached to coil, half attached to valve
10
Modulating control valve (Daikin)
11
All piping, fittings and unions by others (not Daikin
12
except as noted)
Steam check valve and pressure equalizing line (Daikin)
13
Float and thermostatic steam trap (by others)
14
Supply and return coil connection and stub-up unions
15
(by others)
33
15
9
13
15
14
7
Figure 86 & Figure 87
IM 817-7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

AvsAvbAvr

Table of Contents