Typical Valve Packages - Daikin AVV Installation And Maintenance Manual

Classroom unit ventilators floor models digital ready, microtec control (“j” vintage) field controls by others
Hide thumbs Also See for AVV:
Table of Contents

Advertisement

Chilled Water and Electric Heating Coils
Figure 67: Chilled Water (1st Position) and Electric Heating
(Cooling Coils V[5], S[6], W[7]), (Heating Coils 12, 13)
Cooling (Left Hand)
Air Flow
B
A
Plug
S
J
Table 8: Coil Connection Dimensions For Lettered Values
Unit Depth
A
in .
16-5/8
3-3/4
mm
422
95
in .
21-7/8
9
mm
556
229
Table 9: Direct Expansion (DX) Coil G[9] Connection Tubing
07
Unit Series
in
Suction Line OD:
3/4
Liquid LIne OD:
1/4

Typical Valve Packages

The optional factory-supplied Daikin Control Valve(s) for
water applications are either 2-way or 3-way type, and
are shipped separate from the unit ventilator itself to help
avoid shipping damage to the piping of the connection
stub from the weight of the valve, and to provide the
installer with maximum flexibility in making the field
piping connection. Before proceeding, see
through
Figure 92
as applicable, as well as the job-
specific piping drawings.
Notes:
1.
See label furnished on 2-way valve to determine direction of flow through the
valve.
2.
Adhere to the port orientation shown for the 3-way valve.
3.
For hot water applications and chilled water/hot water (2-pipe) applications,
the 2-way valve furnished is normally piped open to the coil; the 3-way valve
is piped normally open to the coil.
4.
For chilled water applications, the 2-way valve furnished is normally piped
closed to the coil; the 3-way valve is piped normally closed to the coil.
5.
The 3-way valve is generally selected for diverting water back to the return
main, where a constant pump head pressure is required.
6.
All water coil stubs are 7/8" I.D. female sweat. Coil connections terminate 9"
(229mm) from the end of the unit. Hot water connections may be same end as
cooling coil connections, but are recommended to be at opposite ends from
each other. When using MicroTech controls, they must be at opposite ends.
www.DaikinApplied.com
Vent
R
13-3/4"
(350mm)
8-1/2"
(216mm)
B
C
D
12-1/4
4-7/8
7-3/4
311
124
198
17-1/2
10-1/8
13
445
257
330
10
mm
in
mm
19
3/4
19
6.35
1/4
6
Figure 69
Direct Expansion and Electric Heating Unit
Figure 68: Direct Expansion (1st Position) and Electric
Heating (Cooling Coils G[9]), (Heating Coils 12, 13)
Cooling (Left Hand)
J
1
Dimensions
E
F
G
1-5/8
10-1/8
2-3/4
41
257
70
6-7/8
15-3/8
8
175
391
203
13
15
in
mm
in
mm
7/8
22
7/8
22
3/8
10
3/8
10
Face & Bypass End of Cycle Valves
2-Way End of Cylce Valve
When piping the 2-Way End of Cycle valve, refer to label
to determine the direction of flow. The valve should be
installed so that there is a 2" (51mm) minimum clearance
to remove the actuator from the valve body. Provide
unions for removal of unit coil and/or control valve as
a future service consideration. Hot water connections
may be same end as cooling coil connections, but are
recommended to be opposite end to facilitate piping.
When using MicroTech® controls, they must be opposite
end. The End of Cycle valve accessory must be field
installed on the unit for which it was selected.
23
Air Flow
LL = Liquid Line
D
SL = Suction Line
LL
11-3/4"
SL
(299mm)
7-1/4"
(184mm)
C
H
I
J
2-7/8
5-5/8
3
73
143
76
8-1/8
10-7/8
8-1/4
206
276
210
K
5
127
10-1/4
260
IM 817-7