MicroTech Wall Mounted Sensor

WARNING
Rigorously adhere to field wiring procedures regarding proper
lockout and tagout of components.
WARNING
To avoid electrical shock, personal injury or death:
1. Installer must be qualified, experienced technician.
2. Disconnect power supply before installation to prevent
electrical shock and damage to equipment.
3. Make all connections in accordance with electrical wiring
diagrams, and in compliance with national and local codes.
Use copper conductors only.
4. Do not exceed ratings of the device. This is a low voltage
device: Never apply more than 12VAC/VDC to any lead or
damage will result.
5. Avoid locations where excessive moisture, corrosive fumes,
or vibrations are present.
Note: Avoid placing wall sensor near drafty areas such as doors
or windows. Avoid external walls, or dead spots near
exposed columns. Avoid direct sunlight on wall sensor.
Figure 106: Wall Mounted Temperature Sensor
When Using A Remote Temperature
Sensor
If a decision is made to use a Wall Mounted Temperature
Sensor instead of the unit mounted room air sensor then
placement of the Remote Wall Mounted Temperature
Sensor is critical for proper room temperature sensing (see
Figure 107
and
Figure
108). The UVC is capable of using
one of four remote wall mounted temperature sensors.
It is recommended that additional wires be pulled to
compensate for potential wire breakage or future options.
6-Button Digital Adustable Sensor (PN 910247458) 8-wires
4-Button Digital Adustable Sensor (PN 910247448) 6-wires
The Basic Sensor with setpoint adjustment (PN
910247453) 4-wires
The Basic Sensor (PN 910247450) 3-wires
NOTICE
For sensor terminal wiring details see the installation manual specific
to the sensor being used.
www.DaikinApplied.com
Figure 107: Correct Wall Sensor Locations
Window Exposure
Interior Wall
Window Exposure
Interior Wall
Figure 108: Incorrect Unit and Wall Sensor Locations
Window Exposure
Unit
Interior Wall
Cubicle Wall
Interior Wall
Interior Wall
Table 36: Max Sensor Wire Length and Gauge
Maximum sensor wire length for less than 1°F error
Gauge
14 AWG
16 AWG
18 AWG
20 AWG
22 AWG
47
= Correct Sensor Location
Window Exposure
Unit
Interior Wall
Interior Wall
= Incorrect Sensor Location
Shelving
File Cabinet
Interior Wall
Shelving
Window Exposure
Window Exposure
Length
800 ft. (244 m)
500 ft. (152 m)
310 ft. (94 m)
200 ft. (61 m)
125 ft. (38 m)
IM 817-7