6. Operation
6.4. Provisioning Device menus

De-provisioning

To de-provision the transmitter from the network and reset all settings to their default factory
values, select Reset Device to Defaults. To simply remove the device from the network select the
transmitter in the WDM and click Delete. This will remove the device from the network and you
will have to manually accept it back onto the network via the WDM interface if you want it to re-
join the same network. This will preserve the settings and Key data etc. If the device is to be
moved to a different ISA100 Network then the only option is to Reset Device to Defaults, and
provision it for the new network. In this case any custom settings will have to be re-applied once
the transmitter is on the new network.
To reset to defaults, perform the following steps:
Select Provisioning Data (under Advanced Options) when:
The Provisioning Device has keys from one system, but you are using provision device on
another system, or
you want to clear all keys so that you cannot deploy any more keys without going to the
Wireless System Gateway user interface and getting more.
For more details on keys, refer to the One Wireless documents in

Read Device Information

Use this to read the transmitter's information shown in
Similar to quick view parameters on the transmitter display.
62

Figure 6-3: Read Device Information