The upper and lower calibration points indicate the upper and lower pressure value that will
correspond the upper and lower scale value respectively.
Flow = (scale EU100 – scale EU0) * sqroot(( DP – Cal Lower) / (Cal Upper – Cal Lower)) –
scale EU0 for DP > cal Lower
Flow = (scale EU100 – scale EU0) * sqroot((Cal Lower - DP) / (Cal Upper – Cal Lower)) – scale
EU0 for DP < -cal Lower
Flow = 0 for DP < abs ( cal lower)
Where scale EU100 and scale EU0 are in flow units and Cal Upper and Cal Lower are in
pressure units.
The square root function is automatically employed for conversion from pressure to flow scale
units. Calibration units are always in pressure units.
Revision 2
Description
Kilograms per centimeter square
Inches H2O
Inches H2O referenced to 4˚C
Inches H2O referenced to 68˚F
millimeters H2O
millimeters H2O referenced to 4˚C
millimeters H2O referenced to 68˚F
Feet H2O
Feet H2O referenced to 4˚C
Feet H2O referenced to 68˚F
Inches mercury
Inches mercury referenced to 0˚C
millimeters mercury
millimeters mercury referenced to 0˚C