TRUTH TABLE

Overview
STO Active
Abnormal
one-channel
operation
detection
STO Inactive
Drive
unpowered
AC30 series Variable Speed Inverter
STO Input A
STO Input B
X10/01
X10/03
0V
0V
24V
0V
0V
24V
24V
24V
Don't care
Don't care
Drive Function
Drive cannot start or supply power to its motor. STO trip
reported.
This is the intended safe state of the product with correct
dual-channel operation.
Drive cannot start or supply power to its motor. STO trip
reported. If either of these conditions persists for more than
3.0 seconds (the maximum fault detection time), the STO
function will lock into a fault state. The drive cannot start until
the fault is rectified; all power is removed and reapplied (both
mains and any auxiliary 24V dc power).
This is single channel operation and thus deemed not as
intended for category 3 / PLe / SIL3 structure
implementation.
Drive is enabled to run under software control. The drive can
supply power to its motor.
Drive cannot start or supply power to its motor.
6-11
Safe Torque Off
STO Status Output
X10/05, X10/06
ON
OFF
OFF
OFF