5-4
Associated Equipment

AC Motor Chokes

The maximum rate of rise of Volts (dv/dt) present on the motor terminals of the inverter, can be as high as 10,000V/µs. This can be
reduced by adding a motor choke in series with the motor.
Installations with long cable runs may suffer from nuisance overcurrent trips, refer to Appendix C Compliance - Cabling Requirements for
maximum cable lengths. An output choke may be fitted in the inverter output to limit parasitic capacitive current to earth. Screened cable
has a higher parasitic capacitance to earth and may cause problems in shorter runs. Contact Parker for recommended choke values.
Motor Power (kW)
0.75
1.1
1.5
2.2
4.0
5.5
7.5
11
15
18
22
30
37
45
55
75
90
110
132
Choke Inductance
RMS Current Rating
2mH
7.5A
0.9mH
22A
0.45mH
33A
0.3mH
44A
50µH
70A
50µH
99A
50µH
99A
50µH
243A
50µH
360A
Contact Parker Hannifin Manufacturing Limited for further information
Parker Part No.
CO055931
CO057283
CO057284
CO057285
CO055193
CO055253
CO055253
CO057960
CO387886