Analog Input Units
108
- -10 to 10 V
The --10- to 10-V range corresponds to the hexadecimal values F448 to 0BB8
(--3000 to 3000). The entire data range is F31C to 0CE4 (--3300 to 3300). A
negative voltage is expressed as a two's complement (16 bits). If the line is
disconnected, the data will be the same as an input of 0 V (0000 Hex).
0CE4 (3300)
0BB8 (3000)
--11 V --10 V
0 to 10 V
The 0- to 10-V range corresponds to the hexadecimal values 0000 to 1770 (0 to
6000). The entire data range is FED4 to 189C (--300 to 6300). A negative voltage
is expressed as a two's complement (16 bits). If the line is disconnected, the data
will be the same as an input of 0 V (0000 Hex).
Converted data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0000 (0)
--0.5 V
FED4 (--300)
0 V
0 to 5 V
The 0- to 5-V range corresponds to the hexadecimal values 0000 to 1770 (0 to
6000). The entire data range is FED4 to 189C (--300 to 6300). A negative voltage
is expressed as a two's complement (16 bits). If the line is disconnected, the data
will be the same as an input of 0 V (0000 Hex).
Converted data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0000 (0)
--0.25 V
0 V
FED4 (--300)
Converted data
Hexadecimal (Decimal)
0000 (0)
0 V
F448 (--3000)
F31C (--3300)
Section
7-1
Voltage
10 V 11 V
Voltage
10 V 10.5 V
Voltage
5 V 5.25 V