Port
Phenomenon
Electrostatic discharge
(ESD)
Radiated EM field
Enclosure
Rated power frequency
magnetic field
Burst
Surge
I/O signal/control
Conducted RF
1. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering.
2. Excluding auxiliary switch function, which meets Performance Criteria B.
Certification Body
Intrinsically Safe
Ex ia Intrinsically Safe
Class I,II,III Division 1 GP A,B,C,D,E, F,G per
drawing GE42818 T5
Natural Gas Approved
Explosion Proof
Class I Division 1 GP B,C,D T6
CSA
Natural Gas Approved
Class I Division 2 GP A,B,C,D T6
Class II Division 1 GP E,F,G T6
Class II Division 2 GP F,G T6
Class III
Natural Gas Approved
Certification Body
Intrinsically Safe
Class I,II,III Division 1 GP A,B,C,D,E,F,G per
drawing GE42819 T5
Natural Gas Approved
Explosion Proof
Class I Division 1 GP B,C,D T6
FM
Natural Gas Approved
Class I Division 2 GP A,B,C,D T6
Class II Division 1 GP E,F,G T6
Class II Division 2 GP F,G T6
Class III
Natural Gas Approved
Certificate
Intrinsically Safe
Gas
Ex ia IIC T5/T6 per drawing GE42990
Natural Gas Approved
Flameproof
Gas
IECEx
Ex d IIC T5/T6
Natural Gas Approved
Type n
Gas
Ex nC IIC T5/T6
Natural Gas Approved
September 2010
Introduction and Specifications
Table 1-3. EMC Summary Results—Immunity
Basic Standard
4 kV contact
IEC 61000-4-2
8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
IEC 61000-4-3
1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
IEC 61000-4-8
30 A/m at 50/60Hz
IEC 61000-4-4
1 kV
IEC 61000-4-5
1 kV (line to ground only, each)
IEC 61000-4-6
150 kHz to 80 MHz at 3 Vrms
Table 1-4. Hazardous Area Classifications—CSA (Canada)
Certification Obtained
Table 1-5. Hazardous Area Classifications—FM (United States)
Certification Obtained
Table 1-6. Hazardous Area Classifications—IECEx
Certification Obtained
Test Level
Entity Rating
Temperature Code
Vmax = 30 VDC
Imax = 226 mA
T5(Tamb v 80_C)
Ci = 5 nF
Li = 0.55 mH
- - -
T6(Tamb v 80_C)
- - -
T6(Tamb v 80_C)
Entity Rating
Temperature Code
Vmax = 30 VDC
Imax = 226 mA
Ci = 5 nF
T5(Tamb v 80_C)
Li = 0.55 mH
Pi = 1.4 W
− − −
T6(Tamb v 80_C)
− − −
T6(Tamb v 80_C)
Entity Rating
Temperature Code
Ui = 30 VDC
Ii = 226 mA
T5(Tamb v 80_C)
Ci = 5 nF
T6(Tamb v 75_C)
Li = 0.55 mH
Pi = 1.4 W
T5(Tamb v 80_C)
− − −
T6(Tamb v 75_C)
T5(Tamb v 80_C)
− − −
T6(Tamb v 75_C)
(1)
Performance Criteria
Point-to-Point
Multi-drop
(2)
A
A
A
A
A
A
(2)
A
A
B
B
A
A
Enclosure Rating
Type 4X, IP66
Single Seal Device
Type 4X, IP66
Single Seal Device
Type 4X, IP66
Single Seal Device
Enclosure Rating
NEMA 4X
NEMA 4X
NEMA 4X
Enclosure Rating
IP66
IP66
IP66