DVC6200 Digital Valve Controller
Actuator
Actuator Model
Manufacturer
585C & 585CR
657
667
4
1051 & 1052
Fisher
1061
1066
1066SR
2052
3024
Air to Extend
Air to Retract
Baumann
Rotary
NOTE: Refer to figure 2-3 and table 4-8 for feedback connection (magnet assembly) information.
1. X = Expert Tuning. Proportional Gain = 4.2; Velocity Gain = 3.0; Minor Loop Feedback Gain = 18.0
2. Values shown are for Relay A and C. Reverse for Relay B.
D Press Integ Enable—Yes or No. Enable the
pressure integral setting to improve static
performance by correcting for error that exists
between the pressure target and actual pressure.
Pressure Integral Control is disabled by default.
D Press Integ Gain—Pressure Integral Gain
(also called reset) is the gain factor applied to the
time integral of the error signal between desired
and actual pressure. Changing this parameter will
also change the tuning set to Expert.
38
Table 4-5. Actuator Information for Initial Setup
Actuator Size
25
50, 60
60, 80
100, 130
30
34, 40
45, 50
46, 60, 70, 76, &
80-100
30
34, 40
45, 50
46, 60, 70, 76, &
80-100
20, 30
33
40
60, 70
30
40
60
68, 80, 100, 130
20, 27, 75
20
27, 75
1
2
GA 1.21
GA 1.31
GA 1.41
225
750
GX
1200
16
32
54
10
25
54
Starting
Actuator Style
Tuning Set
Piston Dbl w/ or w/o
F
Spring. See actuator
J
instruction manual and
L
nameplate.
M
H
K
Spring & Diaphragm
L
M
H
K
Spring & Diaphragm
L
M
H
I
Spring & Diaphragm
K
M
J
K
Piston Dbl w/o Spring
L
M
Piston Dbl w/o Spring
Specify
G
Piston Sgl w/Spring
L
H
Spring & Diaphragm
J
E
Spring & Diaphragm
H
K
(1)
X
K
Spring & Diaphragm
M
C
E
H
Spring & Diaphragm
E
H
J
Tvl/Press Control (1-2-2-2)
D Tvl/Press Select
Travel/Pressure Select determines if the instrument
is set up for position or pressure control. Select
Travel, Pressure, Travel with Pressure
Fallback/Auto recovery or Travel with Pressure
Fallback/Manual Recovery. If the travel sensor
fails, and Travel with Pressure Fallback/Auto
Recovery is selected, it will return to travel control
when the travel sensor starts working again. Travel
with Pressure Fallback/Manual recovery will stay in
Travel Sensor Motion
(2)
Relay A or C
User Specified
Away from the top of the instrument
Towards the top of the instrument
Clockwise or
Away from the top of the instrument
Depends upon pneumatic connections. See
description for Travel Sensor Motion
Depends upon pneumatic connections. See
description for Travel Sensor Motion
Travel Sensor
Mounting Style
Motion
A
Clockwise
B
Counterclockwise
C
Counterclockwise
D
Clockwise
Clockwise
Counterclockwise
For P
operating mode (air opens),
o
Counterclockwise
For P
operating mode (air closes), Clockwise
s
Air to
Open
Close
Counterclockwise
Clockwise
Towards the top of the instrument
Away from the top of the instrument
Specify
September 2010