Wt-4000 Series Pneumatic-To-Ddc Room Thermostat Configuration Parameters - Johnson Controls WT-4002-MCR Installation Instructions Manual

Wt-4000 series pneumatic-to-direct digital control (ddc) room thermostats
Table of Contents

Advertisement

WT-4000 Series Pneumatic-to-DDC Room
Thermostat Configuration Parameters
The variables included in Table 3 define the
WT-4000 Series Pneumatic-to-DDC Room Thermostat
configuration parameters and regulate room thermostat
operation.
Table 3: WT-4000 Series Room Thermostat Configuration Parameters (Part 1 of 2)
Parameter
Occupied Mode
Setpoint value
Comfort Zone upper delta;
default = 3F° (1.8C°)
Comfort Zone lower delta;
default = 3F° (1.8C°)
Unoccupied Mode
Constrained float upper limit;
default = 85°F (29°C)
Constrained float lower limit;
default = 55°F (13°C)
Override Mode
Override duration;
default = 120 minutes
Override Mode
Comfort Zone upper delta;
default = 14F° (8.4C°)
Override Mode
Comfort Zone lower delta;
default = 14F° (8.4C°)
Other Parameters
Network configuration
(Net Config)
Operational modes
Dead zone delta;
default = 1F° (0.6C°)
Room thermostat protection
zone – upper limit;
default = 95°F (35°C)
Room thermostat protection
zone – lower limit;
default = 40°F (4°C)
Default Occupied Mode start
time in the event of wireless
communication failure;
default = 06:00 A.M.
WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats Installation Instructions
Description
Zone setpoint temperature
Upper temperature bound on deviation from configuration
parameters setpoint during Occupied Mode
Lower temperature bound on deviation from parameter setpoint
during Occupied Mode
Defines upper temperature limit in Unoccupied Mode;
HVAC equipment remains off while the zone temperature is
between the upper and lower limits
Defines lower temperature limit in Unoccupied Mode;
HVAC equipment remains off while zone temperature is
between the upper and lower limits
Room thermostat override duration (240 minute maximum
duration); after time limit expires, room thermostat goes into
regularly scheduled mode
Comfort Zone upper delta during Override Mode
Comfort Zone lower delta during override Mode
CH: To change the radio channel number; default = 11
GI: To change the device network group ID; default = 111.111
DI: To change the unique thermostat device ID; default = 71.40
1: Occupied
2: Unoccupied
Temperature range around setpoint, to prevent HVAC from
chattering
Maximum temperature allowed in zone; fail-safe feature
applicable to all zones
Minimum temperature allowed in zone; fail-safe feature
applicable to all zones
Time of day (0 to 24 hours) in the event the room thermostat
goes offline for an extended duration
23
Configuration
Method
Configuration tool
Configuration tool
Configuration tool
Configuration tool
Configuration tool
Configuration tool
Configuration tool
Configuration tool
Configuration tool,
room thermostat
Factory configured
Configuration tool
Factory configured
Factory configured
Factory configured